Vaillant flexoTHERM 15kW 400v ground source heat pump
- Description
- SPECIFICATIONS
- MANUALS
- DELIVERY
- WARRANTY
Description
Contact us on: 01260 228 822
email us at info@theheatpumpwarehouse.co.uk

flexoTHERM can be connected to either a ground collector or borehole system to provide efficient generation of heating and hot water.
General information
Connect with a Standard Pre-Plumbed Cylinder for an eco-friendly, low cost hot water solution. With its sleek design and pre-plumbed architecture, the space requirements for the pre-plumbed hot water cylinder have been reduced dramatically.
Unvented Cylinders & Smart Cylinders can also be used in conjunction with our Air Source Heat Pumps.
Features & Benefits
- Available in 230V and 400V – 230V heat pump is available in 5, 8 and 11kW models. 400V heat pump is available in 5, 8, 11, 15 and 19kW models.
- More power, more efficiency – Integrated EVI super compressor, injects additional refrigerant into the compression cycle
- Exceptionally quiet – With noise levels as low as a modern refrigerator – 42dB(A), flexoTHERM has earned the ‘Quiet Mark’ approval (excludes 230V range)
- High quality and sustainable – Green iQ technology aids in future-proofing the product and ensures optimum efficiency, performance and sustainability
- Ability to cascade up to seven flexoTHERM heat pumps – Suitable for larger domestic and commercial properties
- Extended capabilities and flexibility – Modular design gives flexoTHERM greater sustainability and flexibility with accessories to enable connection to either air or water sources.
| Technical data | Unit | 5kW 230V | 8kW 230V | 11kW 230V | 5kW 400V | 8kW 400V | 11kW 400V | 15kW 400V | 19kW 400v |
|---|---|---|---|---|---|---|---|---|---|
| Product dimensions (H x D x W) | mm | 1183 x 595 x 600 | 1183 x 595 x 600 | 1183 x 595 x 600 | 1183 x 595 x 600 | 1183 x 595 x 600 | 1183 x 595 x 600 | 1183 x 595 x 600 | 1183 x 595 x 600 |
| Weight, with packaging | kg | 161 | 176 | 188 | 155 | 170 | 178 | 185 | 197 |
| Weight, without packaging | kg | 151 | 166 | 178 | 145 | 160 | 168 | 176 | 187 |
| Weight, ready for operation | kg | 157 | 173 | 185 | 151 | 167 | 175 | 187 | 200 |
| Sound power level B0/W35 EN 12102/EN 14511 LWI in heating mode |
dB(A) | 43.8 | 45.6 | 48.5 | 39.8 | 42.4 | 45.2 | 49.9 | 48.4 |
| Inrush current (with inrush current limiter) | A | 15 | 19 | 60 | 15 | 19 | 22 | 26 | 30 |
| Energy-related Product 35°C* | band | A+++ | |||||||
| Energy-related Product 55°C* | band | A+++ | |||||||
| MCS SCoP performance table | |||||||||
| 35°C | 4.67 | 4.64 | 4.73 | 4.97 | 5.34 | 5.30 | 5.18 | 4.87 | |
| 40°C | 4.15 | 4.14 | 4.23 | 4.40 | 4.74 | 4.68 | 4.60 | 4.36 | |
| 45°C | 3.64 | 3.65 | 3.73 | 3.83 | 4.14 | 4.07 | 4.02 | 3.85 | |
| 50°C | 3.50 | 3.52 | 3.61 | 3.66 | 3.99 | 3.89 | 3.88 | 3.76 | |
| 55°C | 3.36 | 3.38 | 3.49 | 3.49 | 3.83 | 3.72 | 3.74 | 3.68 | |
flexoTHERM brochure
flexoTHERM Installer leaflet
flexoTHERM 400V installation manual
flexoTHERM 230V installation manual
The Vaillant renewables range
flexoTHERM 230V heat pump technical specification
flexoTHERM 400V heat pump technical specification
flexoTHERM user manual